Schneider LC1D18M7 TeSys D Contactor
The Schneider Electric LC1D18M7 is a three pole TeSys D contactor rated 18 A in AC-3 duty, suitable for motors up to 7.5 kW at 400 V.
- Brand
- Schneider Electric
- Category
- Contactors
- Series
- TeSys D
- Condition
- New Original
- Availability
- In Stock
- Lead Time
- 24-72 h dispatch
- MOQ
- 1 pc
- Pricing
- Please request quote
Description
The Schneider Electric LC1D18M7 is a three pole TeSys D contactor rated 18 A in AC-3 duty, suitable for motors up to 7.5 kW at 400 V. The M7 suffix denotes an AC 220 V 50/60 Hz coil. The device has three normally open main contacts and one normally open plus one normally closed auxiliary contact integrated in the front, and mounts on a 35 mm DIN rail or on a panel plate. TeSys D contactors are the reference motor switching device in European control panels and accept the LRD thermal overload relay family directly.
- Direct mounting of LRD thermal overload relays
- AC 220 V 50/60 Hz coil
- Integrated 1 NO + 1 NC auxiliary contacts
- DIN rail or panel plate mounting
Technical Specifications
| Product type | AC contactor, 3 pole |
|---|---|
| Series | TeSys D |
| Rated operational current AC-3 (400 V) | 18 A |
| Rated operational power AC-3 (400 V) | 7.5 kW |
| Rated operational current AC-1 (60 C) | 32 A |
| Rated insulation voltage | 690 V |
| Main contacts | 3 NO |
| Auxiliary contacts | 1 NO + 1 NC |
| Coil voltage | AC 220 V, 50/60 Hz |
| Mounting | 35 mm DIN rail or panel plate |
| Compatible overload relays | LRD thermal overload relay range (direct mounting) |
| Standards | IEC/EN 60947-4-1, UL 508, CSA |
Values are quoted as published by Schneider Electric. Parameters not documented by the manufacturer are shown as N/A rather than estimated.
Dimensions & Drawing
No 2D drawing on file
| Width (W) | 45 mm |
|---|---|
| Height (H) | 85 mm |
| Depth (D) | 92 mm |
| Weight | 0.36 kg |
Confirm dimensions against the Schneider TeSys D catalogue before panel layout.
Series Information
TeSys D is the Schneider Electric contactor range from 9 A to 150 A AC-3. The family shares a common accessory programme of auxiliary contact blocks, mechanical interlocks, surge suppression modules and direct-mount LRD thermal overload relays, allowing the same panel architecture to scale across motor sizes.
Cross Reference & Alternatives
Replaces / supersedes
- LC1D1810 series legacy ordering codes
Related / interoperable
- LC1D18B7 (24 V AC coil)
- LC1D18P7 (230 V AC coil)
Cross references are listed only where the relationship is documented by the manufacturer. They are not inferred.
Application Scenarios
- Pump and fan motor starters
- Compressor control
- Conveyor drives
- Packaging machinery
- Building services motor control
Downloads
Contact us for datasheet
Request documentsFAQ
What does the M7 suffix mean?
Which overload relay mounts directly?
Can you supply this as a complete starter?
Related Products
Need this part? Send us an RFQ.
Send the part numbers and quantities - we reply with price, availability and lead time within 24 hours.